Datasheet 搜索 > 电路保护器件 > Phoenix(菲尼克斯) > 2800788 数据手册 > 2800788 数据手册 2/5 页
2800788
1545.683
导航目录
  • 典型应用电路图在P5
  • 技术参数、封装参数在P1P2P3P4
2800788数据手册
Page:
of 5 Go
若手册格式错乱,请下载阅览PDF原文件
https://www.phoenixcontact.com/us/products/2800788
09/10/2014Page2/5
Surge protection device-PT-IQ-2X1+F-24DC-UT-2800788
Technical data
Dimensions
Depth 77.5 mm
Horizontal pitch 1 Div.
Ambient conditions
Ambient temperature (operation) -40 °C ... 70 °C
Ambient temperature (storage/transport) -40 °C ... 85 °C
Degree of protection IP20
General
Housing material PA 6.6
Inflammability class according to UL 94 V0
Color black
Mounting type DIN rail mounting
Type DIN rail module, two-section, divisible
Direction of action
Line-Line & Line-Signal Ground/Shield & optional Signal Ground/Shield-
Earth Ground
Protective circuit
IEC test classification C1
C2
C3
D1
Nominal voltage U
N
24 V
Maximum continuous operating voltage U
C
30 V DC
21 V AC
Nominal current I
N
1000 mA (Up to 45°C)
Operating effective current I
C
at U
C
≤ 1 mA (per path)
Residual current I
PE
≤ 1 µA
Nominal discharge current I
n
(8/20) µs (Core-Earth)
10 kA
Total surge current (8/20) µs 20 kA
Impulse discharge current (10/350)˽µs, peak value l
imp
2.5 kA
Voltage protection level U
P
(Core-Earth)
≤ 800 V (C1 - 1 kV/500 A)
≤ 950 V (C2 - 10 kV / 5 kA)
≤ 780 V (C3 - 25 A)
≤ 950 V (C3 - 50 A)
Voltage protection level U
P
(Core-GND)
≤ 75 V (C1 - 1 kV/500 A)
≤ 135 V (C2 - 10 kV / 5 kA)
≤ 55 V (C3 - 25 A)
≤ 60 V (C3 - 50 A)